Voltage Stability Assessment of a Grid-Connected Wind Turbine on the BEDC Network Using Newton–Raphson Load Flow Analysis

Efetobor Mathew Ufuoma, Anazia Emmanuel Aninye, Aghara Jachimma Vincent, Ibeh Charles Austeen, Anionovo Ugochukwu Edebeani · Pages 4079-4093 · August 22, 2026

ISSN 2992-4383

Authors

  • Efetobor Mathew Ufuoma Corresponding author
  • Anazia Emmanuel Aninye
  • Aghara Jachimma Vincent
  • Ibeh Charles Austeen
  • Anionovo Ugochukwu Edebeani

Abstract

This study evaluates the voltage stability of a grid-connected wind turbine integrated into the Benin Electricity Distribution Company (BEDC) network using Newton–Raphson load flow and transient simulations in PowerWorld Simulator. The network was analyzed under steady-state and three-phase fault conditions before and after wind turbine integration. A three-phase fault was applied to Feeder II of the Amukpe 132/33 kV substation. Results showed improved voltage stability following wind turbine integration. The minimum voltage increased from 0.2981 p.u. to 0.31153 p.u., while stabilization time decreased from approximately 4.7503 s to 2.191762 s. In addition, the maximum voltage angle reduced from 6.32887° to 2.53556°, with fewer system oscillations observed. These findings indicate that wind energy integration can improve transient voltage response, enhance damping, and strengthen the overall stability and reliability of the BEDC network.

Keywords

Voltage Stability, Wind Energy, BEDC Network, Newton–Raphson Method, PowerWorld Simulator, Renewable Energy Integration, Transient Stability.

How to cite

No formats match your search.

Pick a style from the searchable list. Download uses the format currently selected.

Reference managers: RIS · BibTeX · EndNote

In-text (APA): (Ufuoma et al., 2026) · Ufuoma et al. (2026)